XM3.1-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-918-HP
Firmware V1.02.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Rest
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 123.55 V
Current 6.95 A
Power 698 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 4,959 Wh
Output
Voltage 86.68 V
Power 599 W
Apparent Power 663.10 VA
Frequency 60.02 Hz
Percent Load 42.50 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 7.65 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.70 V/cell
Reduced Peak Mode Disable
Total Standby Events 90
Time Since Last Standby Event 297d 13h:45m
Time in Last Standby Event 0d 3h:59m
Total Time in Standby 889 min
Standby Events Since Reset 27
Time in Standby Since Reset 392 min
Time Since Reset 1,210 day(s)
Total Run Time 1,210 day(s)
Transformer Run Time 1,210 day(s)
Total Downtime 0d 0h:02m
Oil Cap Lifespan Consumed 48.4 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 23 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 